Julabo LC 6 Programmable Controller Bedienungsanleitung Seite 35

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 50
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 34
35
8.5. Analog inputs/outputs
or
This submenu enables setting of the input and output values
for the programmer input and the temperature recorder outputs
of socket REG+E-PROG (21).
Press enter
to select the inputs/outputs submenu.
Use the up/down cursor keys
to select the
desired option and press enter
to open.
Chan.1 voltage output for recorder (V)
Chan.2 voltage output for recorder (V)
Chan.3 current output for recorder (mA)
EPROG external programmer input
First define the desired output value for channels 1 to 3
:
Press the P-key
to select the desired output value and set
with enter
Setpoint active setpoint temperature
(T1, T2, integr. programmer/ext. programmer)
ActInt internal actual temperature value
(bath temperature)
ActExt external actual temperature value
(external sensor)
Power periodic or intermittent heating or cooling
Then select the display size for channels 1 to 3:
Channel 1 and 2 voltage outputs
Assign the voltage values of 0 V to the lowest and 10 V to
the highest necessary temperature or power rating required
as an output value (°C or %).
Current output channel 3
Assign the current values 0 mA or 4 mA to the lowest and
20 mA to the hightest temperature or power rating required
as an output value (°C or %).
The current output offers 2 ranges for selection:
0 to 20 mA and 4 to 20 mA.
Select the desired range by pressing the P-key
and set with enter
.
The LCD display changes automatically.